When GFCI'S Are Required in Kitchens and Bathrooms
Required Receptacles in Residential Washrooms Rule 26-710(f)
Rule 26-710(f) states that at least one receptacle shall be installed within 1 m of the washbasin located in each bathroom or washroom.
GFCI Protection of Kitchen Counter Receptacles
The 2002 edition of the Ontario Electrical Safety Code includes an Ontario amendment to Rule 26-700, which requires Ground Fault Circuit Interrupter (GFCI) protection for Kitchen Counter receptacles effective January 1, 2003.
The new Subrule (26-700(12) states that effective January 2003:
(12) Receptacles located in kitchens and installed within 1 m of a kitchen sink along the wall behind counter work surfaces shall be protected by a ground fault circuit interrupter of the Class A type. Appendix B note: Distance of 1 m is measured from edge of kitchen sink. The following guidelines shall be used for consistent interpretation and application of this new subrule effective January 1, 2003.
1. This rule applies to all receptacle installations located within 1 m of a kitchen sink along the wall behind counter work surfaces where the plans or application for inspection is received on or after January 1, 2003.
2. This rule applies to all kitchens.
2.1. Kitchen is defined as “a place (as a room) with cooking facilities”
2.2. A cooking facility is defined as a range or stove (electric or gas supply) for cooking. Hot plates, microwaves, etc. are not defined as a cooking facility for application of this rule.
3. In dwelling units, Rules 26-712(d) and 26-722(b) require that kitchen counter receptacles be split receptacles connected to multi-wire 15 amp branch circuits. Rule 26-726 permits the installation of 5-20 RA (T-slot) receptacles connected to single 20 amp branch circuits as an alternative to split receptacles and circuits.
4. The adjacency requirement as stated in Rules 26-722(b) and 26-726(3) has been deemed to offer no added safety value to an installation.
The Canadian Electrical Code has deleted the adjacency requirement in the next edition. ESA along with the Ontario Provincial Code Council has reviewed the Part I direction and the adjacency requirement in Rule 26-722 for counter receptacles is no longer applicable”.
Ground Fault Circuit Interrupter Protection on Receptacles within 3 m of Washbasins, Bathtubs or Showers
To assist in consistent application of this rule, the intent of the rule is to provide protection against electrical shock hazard when using portable personal grooming appliances.
(1) The requirements of the rule apply to receptacles located in a bathroom or washroom and installed within 3 m of washbasins, bathtubs or showers. In addition to bathrooms and washrooms found in dwelling units, a washroom will be considered as any room containing personal washing facilities found in occupancies such as motels, hotels, golf clubs, barber shops, health clubs, sports facilities, commercial and industrial installations, where the receptacle is at counter height and a personal grooming appliance could be used .
(2) Doctors’ examining rooms, dentists’ offices, laboratories, classrooms and similar areas are not considered as washrooms. However, if there is a bathroom or washroom in a patient care area the receptacle shall be GFCI protected as per subrule 24-106(3).
(3) The rule does not apply to receptacles in combined bath and laundry rooms provided the receptacle is located behind the washing machine at not more than 600 mm from the floor as per Rule 26-710(h)
GFCI Protection of Receptacles in Carports and Garages
Do receptacles located in a carport for a dwelling unit require GFCI protection? Yes, all receptacles located in a carport shall be considered as outdoors and shall be protected by a ground fault circuit interrupter of the Class A type. A carport receptacle is not on an interior surface of a building, it is on the exterior surface facing out, and hence it is outdoors. Rule 26-714(b) says all receptacles installed outdoors and within 2.5 m of grade level… shall be GFCI protected. A well-known dictionary defines a carport as a shelter for an automobile, consisting of a roof extended from the side of a building.
Using the Ontario Building Code for additional guidance, a carport shall be considered as being a shelter for an automobile, consisting of a roof extended from the side of a building and having less than 60% of the perimeter closed in by walls, doors or windows.
The Ontario Building Code states a carport that has more than 60% of the total perimeter enclosed by walls, doors, or windows shall be considered as being a garage. The Ontario Electrical Safety Code does not require GFCI protection of receptacles within a garage however it is recommended that receptacles in a garage that may be used for outdoor appliances be protected by a ground fault circuit interrupter of the Class A type.